Suit for LV/ HV Voltage System
For low voltage system, direct connect up to 690 V (L-L) AC
For high voltage system, support connect up to 65kV
Ture-RMS Measuring Parameter
True-RMS measuring parameters includes:
U, I, P, Q, S, PF, F, kWh, kvarh, kVAh
Demand Calculation
2 kinds of demand modes: fixed block and rolling block
Power Quality Analysis
31st Harmonic analysis, K factor, unbalance etc.
TOU (Multi-tariff billing), Historical Data of 31 Days and 12 Months
TOU, 4 tariffs, 8 time period in 24 hours
Max./ Min. Record (U, I, P, Q*, S*)
Under/ Over Limit Alarm
64M Bit Memory, Build-in Web
Real-time data inquiry by Web
Save monitoring data (Time interval
settable 1min, 5 min, 10min,15min, 30min)
Support FTP for download memory data
CO2 (Carbon Dioxide) Calculation for kWh
Multiple Communication
BACnet MS/TP Protocol (RS485 port)
MODBUS-RTU Protocol (RS485 Port)
MODBUS-TCP/IP Protocol (Ethernet port )
DI / DO
High Accuracy
Active energy: according to IEC62053-22, class 0.5s
Reactive energy: according to IEC62053-23, class 2
Basic Function
|
|||
Real time metering |
Voltage
|
Ua, Ub, Uc, Uab, Ubc, Uca, UL-L avg, UL-N avg
|
|
Current
|
Ia, Ib, Ic, In, Iavg
|
||
Power
|
Pa, Pb, Pc, ∑P, Qa, Qb, Qc, ∑Q, Sa, Sb,Sc, ∑S
|
||
Power Factor
|
PFa, PFb, PFc, ∑PF
|
||
Energy
|
kWh, kvarh, kVAh *
|
||
CO2 (Carbon dioxide)
|
|||
Frequency
|
F
|
||
Demand & Max. Demand
|
Dmd_I, Dmd_P, Dmd_Q ,Dmd_S
|
||
Max./ Min. Value
|
Max./ min. (U, I, P, Q*, S*)
|
||
Multi-tariff Energy *
|
|||
Phase Angle *
|
|||
Power Quality Analysis
|
Unbalance
|
U_unbl *, I_unbl *
|
|
Harmonic (31st )
|
THDu, THDi, TOHDu, TOHDi, TEHDu, TEHDi, HRU *, RHI *
|
||
Harmonic RMS (0-31st )
|
Harmonic RMS-U *, Harmonic RMS-I *, Harmonic RMS-P *
|
||
Harmonic energy (1st -13th )
|
|||
Voltage crest factor, current K factor, Load rate, Voltage deviation, Frequency deviation
Running time record for power-on period and qualified voltage & current * |
|||
Setpoint Alarm
|
Over/ under limit alarm
|
||
3DI +2 DO
|
3 status input + 2 relay output
|
||
RS485
|
Modbus-RTU protocol
|
||
Record Function
|
SOE (event log), Real-time clock ( yyyy-mm-dd hh:mm:ss) *
|
||
Voltage/ frequency deviation, Voltage unbalance record
|
Optional Module
|
|||
SW
|
4 status input (wet contact)
|
LAN
|
64M bit memory + Ethernet TCP/IP
|
SD
|
4 status input (dry contact)
|
AI
|
2 analog input (4-20mA)
|
C *
|
The 2nd RS485
|
AO
|
2 analog output (4-20mA)
|
Ep *
|
2 pulse output
|
BA
|
BACnet MS/TP protocol
|
R
|
2 relay output
|
||
* means some of function can’t be read through BACnet communication port
|
Parameter
|
Accuracy
|
Resolution
|
Measuring Range
|
Voltage |
0.2% |
0.01V |
Direct: 690Vph-ph
|
PT primary: 0.001kV~65kV (settable)
PT secondary: 1~398V (settable) |
|||
Current
|
0.2%
|
0.001A
|
CT primary: 1~9,999A (settable)
CT secondary: 1 A or 5A |
Power
|
0.5%
|
0.1W/var/ VA
|
each phase: 0~649.9MW/ Mvar/ MVA
|
Total: 0~1949.8MW/ Mvar/ MVA
|
|||
Power Factor
|
0.5%
|
0.001
|
-1.000~+1.000
|
Frequency
|
0.01
|
0.01Hz
|
45~ 65 Hz
|
Active Energy
|
0.5%
|
0.1kWh
|
0~ 99,999,999.9 kWh
|
Reactive Energy
|
2.0%
|
0.1kvarh
|
0~ 99,999,999.9 kvarh
|
Apparent Energy
|
1.0%
|
0.1kVAh
|
0~ 99,999,999.9 kVAh
|
THD
|
1.0%
|
0.001
|
0~100.0%
|
Individual Harmonic
|
1.0%
|
0.001
|
0~100.0%
|
Un-balance
|
1.0%
|
0.001
|
0~100.0%
|
Connection mode
|
3-phase 3-wire, 3-phase 4-wire, 1-phase 2-wire
|
Communicati-on |
Modbus-RTU Protocol |
RS485 serial
Baud rate: 2400, 4800, 9600, 19200, 38400bps Address: 1~247 |
Metering
|
True RMS, 1 sec refresh time
|
|||
Input |
Rate current: 1A or 5A
Rate voltage: Direct 120, 220V, 240V, 277V, 398Vph-N (optional) PT secondary: 1~398V (settable) Frequency: 50/ 60Hz |
Modbus-TCP/ IP
|
Ethernet communication port
Support connect 10M/100M ethernet, Modbus TCP/IP, Web, FTP |
|
Overload |
120% of rated, continuously
Instantaneous current: 10 times/ sec Instantaneous voltage: 2 times/ sec |
BACnet MS/TP protocol
|
RS485 serial
Baud rate: 2400, 4800, 9600, 19200, 38400, 57600, 76800bps
Address: 1…127, excluding 99 |
|
Status input
|
Wet contact, external power supply
|
|||
Relay output
|
Node capacity: 250VAC/5A
|
Dimension
(L x W x H) |
F-MPM110:
Panel: 96 x 96 x 13.5 mm Cut-out: 90 x 90 x 58.6 mm (basic) 90 x 90 x 80.1 mm (optional module) F-MPM110-DR: Panel: 96 x 96 x 12 mm Cut-out: 90 x 90 x 58.6 mm (basic) |
|
Pulse output
|
Pulse constant: 1000~9999 programmable
Pulse width: 60~100ms programmable Formula: 1 pulse = (1÷ pulse constant ×PT ×CT) kWh |
|||
Power supply |
85 ~265VAC,85~265VDC (When select P1)
100~420VAC, 100~400VDC (When select P2) |
|||
Power loss
|
<5VA
|
Weight
|
Basic unit: approx 550gr.
Optional module: 50gr. |
|
IP index
|
IP52 (front panel) and IP30 (case)
|
Environment
|
Main Module & and other Modules
|
Operating temperature: -10℃~ +55 ℃
Storage temperature: -40℃~ +70 ℃ Humidity: 5%~95% non-condensing |
Power frequency withstand voltage
|
AC 2KV/minute
|
|||
Insulation resistance
|
≥50MΩ
|
BACnet Module
|
Operating temperature: 0℃~ +50 ℃
Storage temperature: -5℃~ +75 ℃ Humidity: 10%~95% non-condensing |
|
Impulse withstand voltage
|
4kV (peak), 1.2/50uS
|
Standard(EMC)
|
|||
Electrostatic discharge immunity test
|
IEC 61000-4-2,Level 4
|
Surge immunity test (1, 2/50μs~8/20μs)
|
IEC 61000-4-5,Level 3
|
Radiated immunity test
|
IEC 61000-4-3,Level 3
|
Conducted emissions
|
EN 55022,Class B
|
Electrical fast transient /burst immunity test
|
IEC 61000-4-4,Level 4
|
Radiated emissions
|
EN 55022,Class B
|